Wire Size Calculator — Ampacity and Voltage Drop
Electrical & EnergyFind the minimum copper or aluminum conductor for a load, checking both ampacity (NEC Table 310.16) and voltage drop over your run length.
Rates and tables verified: · sources
Last updated: October 2026
A wire has to pass two checks. It must carry the current without overheating — its ampacity. And it must deliver enough voltage at the far end — its voltage drop. On short runs, ampacity usually decides the size. On long runs, voltage drop often forces a larger wire than ampacity alone would need. This wire size calculator runs both checks. Ampacity comes from NEC Table 310.16 (copper and aluminum, 60/75/90°C columns, 30°C ambient, no more than three current-carrying conductors). It applies the NEC 240.4(D) limits on 14, 12 and 10 AWG. Voltage drop uses the DC resistance values in NEC Chapter 9, Table 8, for the round trip. The recommendation is the larger of the two sizes. The temperature column matters. Under NEC 110.14(C), circuits of 100 A or less (or 14–1 AWG conductors) are limited to the 60°C column unless the equipment terminals are listed for 75°C. Larger circuits default to 75°C. The calculator follows that default unless you choose otherwise.
How to Calculate Wire Size
1. Start with the load current. For continuous loads (3 hours or more), multiply by 1.25. 2. Pick the temperature column your terminations allow: usually 60°C up to 100 A, 75°C above. 3. Find the smallest conductor in NEC Table 310.16 whose ampacity covers the design current. For 14–10 AWG, also respect the 240.4(D) overcurrent limits. 4. Calculate voltage drop at the load current: 2 × I × R × L ÷ 1000 for single-phase/DC, or √3 × I × R × L ÷ 1000 for three-phase. 5. If the drop exceeds your limit (3% is a common target), step up in size until it doesn't. Use the larger of the two results.
Formula
Design current I_d = I × 1.25 (continuous) or I
Ampacity check Table 310.16 ampacity(size, material, °C) ≥ I_d
and, for 14–10 AWG, 240.4(D) limit ≥ I_d
Voltage drop VD = k × I × R × L ÷ 1000
k = 2 (single-phase, DC) or √3 (three-phase)
R = Ω per 1,000 ft (Chapter 9 Table 8, 75°C)
L = one-way length (ft)
VD % = VD ÷ V × 100 ≤ limit
Recommended size = larger of (ampacity size, voltage-drop size) Wire Size Examples
Example 1 — 20 A, 120 V, 40 ft, copper
Ampacity (60°C): 12 AWG = 20 A ✓ (240.4(D) limit 20 A) Drop on 12 AWG: 2 × 20 × 1.98 × 40 ÷ 1000 = 3.17 V = 2.6% ✓ Result: 12 AWG copper
Example 2 — Same 20 A circuit, 100 ft run
12 AWG drop: 7.92 V = 6.6% ✗ 10 AWG drop: 4.96 V = 4.1% ✗ 8 AWG drop: 3.11 V = 2.6% ✓ Result: voltage drop governs → 8 AWG copper
Example 3 — 40 A continuous load (EV charger), 240 V, 30 ft, copper, 75°C terminals
Design current: 40 × 1.25 = 50 A Ampacity (75°C): 8 AWG = 50 A ✓ Drop on 8 AWG: 2 × 40 × 0.778 × 30 ÷ 1000 = 1.87 V = 0.78% ✓ Result: 8 AWG copper — if the charger and breaker terminals are listed for 75°C (At 60°C the answer would be 6 AWG: 55 A, drop 0.49%)
Wire Sizing Notes
- › Check the temperature rating printed on the breaker and the equipment terminals. It, not the wire's insulation rating, usually sets the usable ampacity column.
- › Long runs to outbuildings, wells and EV chargers are where voltage drop bites. Check the run length before buying wire.
- › More than three current-carrying conductors in one raceway, or hot locations such as attics and rooftops, need adjustment factors this calculator does not apply. The wire must then be larger.
- › Need the current first? Convert watts, kW or horsepower with the amp calculator.
Ampacity and Resistance Table (NEC 310.16 and Chapter 9 Table 8)
| Size | Cu 60°C | Cu 75°C | Cu 90°C | Al 60°C | Al 75°C | Al 90°C | Cu Ω/kft | Al Ω/kft |
|---|---|---|---|---|---|---|---|---|
| 14 AWG | 15* | 20* | 25* | — | — | — | 3.14 | — |
| 12 AWG | 20* | 25* | 30* | 15* | 20* | 25* | 1.98 | 3.25 |
| 10 AWG | 30* | 35* | 40* | 25* | 30* | 35* | 1.24 | 2.04 |
| 8 AWG | 40 | 50 | 55 | 35 | 40 | 45 | 0.778 | 1.28 |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 | 0.491 | 0.808 |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 | 0.308 | 0.508 |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 | 0.245 | 0.403 |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 | 0.194 | 0.319 |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 | 0.154 | 0.253 |
| 1/0 AWG | 125 | 150 | 170 | 100 | 120 | 135 | 0.122 | 0.201 |
| 2/0 AWG | 145 | 175 | 195 | 115 | 135 | 150 | 0.0967 | 0.159 |
| 3/0 AWG | 165 | 200 | 225 | 130 | 155 | 175 | 0.0766 | 0.126 |
| 4/0 AWG | 195 | 230 | 260 | 150 | 180 | 205 | 0.0608 | 0.1 |
| 250 kcmil | 215 | 255 | 290 | 170 | 205 | 230 | 0.0515 | 0.0847 |
| 300 kcmil | 240 | 285 | 320 | 195 | 230 | 260 | 0.0429 | 0.0707 |
| 350 kcmil | 260 | 310 | 350 | 210 | 250 | 280 | 0.0367 | 0.0605 |
| 400 kcmil | 280 | 335 | 380 | 225 | 270 | 305 | 0.0321 | 0.0529 |
| 500 kcmil | 320 | 380 | 430 | 260 | 310 | 350 | 0.0258 | 0.0424 |
Ampacity in amps, 30°C ambient, ≤3 current-carrying conductors. * Overcurrent protection limited by NEC 240.4(D): 14 Cu 15 A, 12 Cu 20 A, 10 Cu 30 A, 12 Al 15 A, 10 Al 25 A. Resistance: DC, 75°C, stranded, ohms per 1,000 ft.
Assumptions, Sources & Limitations
What this calculator assumes
- Ampacity: NEC Table 310.16 — allowable ampacities of insulated conductors, not more than three current-carrying conductors in raceway, cable or earth, 30°C (86°F) ambient. Values per the 2023 NEC baseline as reprinted in NFPA's 2026-cycle First Draft report; identical to the 2017 NEC values published by Cerrowire for every cell compared.
- Only one ampacity correction is applied: the 125% factor for continuous loads. No ambient-temperature correction (30°C/86°F is assumed) and no adjustment for more than three current-carrying conductors.
- Temperature column "Auto" follows the NEC 110.14(C) default: 60°C for circuits of 100 A or less, 75°C above. Choose 75°C only if every termination is listed for it.
- NEC 240.4(D) small-conductor limits are applied as a maximum current for 14, 12 and 10 AWG.
- Voltage drop: NEC Chapter 9 Table 8 — DC resistance at 75°C (167°F), stranded conductors, ohms per 1,000 ft (uncoated copper; aluminum). Calculated at the actual load current, as a round trip (×2) for single-phase and DC, ×√3 for balanced three-phase. AC reactance is ignored, which slightly understates drop on large conductors.
- Voltage drop limits such as 3% are design recommendations (NEC informational notes), not mandatory code requirements in most jurisdictions.
Not included
- Ambient temperature correction and conductor-bundling adjustment factors (NEC 310.15)
- Motor, HVAC, welder, EV-specific, service and feeder rules that change the required size (e.g. NEC Articles 430, 440, 625)
- Parallel conductors, cable types with lower ratings (e.g. NM cable is limited to the 60°C column), and underground/direct-burial specifics
- Equipment grounding conductor sizing, conduit fill, and box fill
- Local amendments and code editions other than the one cited