Wire Size Calculator — Ampacity and Voltage Drop

Electrical & Energy

Find the minimum copper or aluminum conductor for a load, checking both ampacity (NEC Table 310.16) and voltage drop over your run length.

Rates and tables verified: · sources

Last updated: October 2026

A wire has to pass two checks. It must carry the current without overheating — its ampacity. And it must deliver enough voltage at the far end — its voltage drop. On short runs, ampacity usually decides the size. On long runs, voltage drop often forces a larger wire than ampacity alone would need. This wire size calculator runs both checks. Ampacity comes from NEC Table 310.16 (copper and aluminum, 60/75/90°C columns, 30°C ambient, no more than three current-carrying conductors). It applies the NEC 240.4(D) limits on 14, 12 and 10 AWG. Voltage drop uses the DC resistance values in NEC Chapter 9, Table 8, for the round trip. The recommendation is the larger of the two sizes. The temperature column matters. Under NEC 110.14(C), circuits of 100 A or less (or 14–1 AWG conductors) are limited to the 60°C column unless the equipment terminals are listed for 75°C. Larger circuits default to 75°C. The calculator follows that default unless you choose otherwise.

How to Calculate Wire Size

1. Start with the load current. For continuous loads (3 hours or more), multiply by 1.25. 2. Pick the temperature column your terminations allow: usually 60°C up to 100 A, 75°C above. 3. Find the smallest conductor in NEC Table 310.16 whose ampacity covers the design current. For 14–10 AWG, also respect the 240.4(D) overcurrent limits. 4. Calculate voltage drop at the load current: 2 × I × R × L ÷ 1000 for single-phase/DC, or √3 × I × R × L ÷ 1000 for three-phase. 5. If the drop exceeds your limit (3% is a common target), step up in size until it doesn't. Use the larger of the two results.

Formula

Design current   I_d = I × 1.25 (continuous) or I
Ampacity check   Table 310.16 ampacity(size, material, °C) ≥ I_d
                 and, for 14–10 AWG, 240.4(D) limit ≥ I_d

Voltage drop     VD = k × I × R × L ÷ 1000
                 k = 2 (single-phase, DC) or √3 (three-phase)
                 R = Ω per 1,000 ft (Chapter 9 Table 8, 75°C)
                 L = one-way length (ft)
VD %             = VD ÷ V × 100 ≤ limit

Recommended size = larger of (ampacity size, voltage-drop size)

Wire Size Examples

Example 1 — 20 A, 120 V, 40 ft, copper

Ampacity (60°C): 12 AWG = 20 A ✓ (240.4(D) limit 20 A)
Drop on 12 AWG: 2 × 20 × 1.98 × 40 ÷ 1000 = 3.17 V = 2.6% ✓
Result: 12 AWG copper

Example 2 — Same 20 A circuit, 100 ft run

12 AWG drop: 7.92 V = 6.6% ✗
10 AWG drop: 4.96 V = 4.1% ✗
 8 AWG drop: 3.11 V = 2.6% ✓
Result: voltage drop governs → 8 AWG copper

Example 3 — 40 A continuous load (EV charger), 240 V, 30 ft, copper, 75°C terminals

Design current: 40 × 1.25 = 50 A
Ampacity (75°C): 8 AWG = 50 A ✓
Drop on 8 AWG: 2 × 40 × 0.778 × 30 ÷ 1000 = 1.87 V = 0.78% ✓
Result: 8 AWG copper — if the charger and breaker terminals are listed for 75°C
(At 60°C the answer would be 6 AWG: 55 A, drop 0.49%)

Wire Sizing Notes

Ampacity and Resistance Table (NEC 310.16 and Chapter 9 Table 8)

SizeCu 60°CCu 75°CCu 90°CAl 60°CAl 75°CAl 90°CCu Ω/kftAl Ω/kft
14 AWG15*20*25*———3.14—
12 AWG20*25*30*15*20*25*1.983.25
10 AWG30*35*40*25*30*35*1.242.04
8 AWG4050553540450.7781.28
6 AWG5565754050550.4910.808
4 AWG7085955565750.3080.508
3 AWG851001156575850.2450.403
2 AWG9511513075901000.1940.319
1 AWG110130145851001150.1540.253
1/0 AWG1251501701001201350.1220.201
2/0 AWG1451751951151351500.09670.159
3/0 AWG1652002251301551750.07660.126
4/0 AWG1952302601501802050.06080.1
250 kcmil2152552901702052300.05150.0847
300 kcmil2402853201952302600.04290.0707
350 kcmil2603103502102502800.03670.0605
400 kcmil2803353802252703050.03210.0529
500 kcmil3203804302603103500.02580.0424

Ampacity in amps, 30°C ambient, ≤3 current-carrying conductors. * Overcurrent protection limited by NEC 240.4(D): 14 Cu 15 A, 12 Cu 20 A, 10 Cu 30 A, 12 Al 15 A, 10 Al 25 A. Resistance: DC, 75°C, stranded, ohms per 1,000 ft.

Assumptions, Sources & Limitations

What this calculator assumes

Not included

Sources (checked October 5, 2026)

Frequently Asked Questions

What size wire do I need for 20 amps? +
For a typical 20 A branch circuit, 12 AWG copper is the minimum: its 60°C ampacity is 20 A, and NEC 240.4(D) limits it to a 20 A breaker. On runs longer than about 50 ft at 120 V, voltage drop may call for 10 AWG. Enter your length above to check.
What size wire for a 50 amp circuit? +
In copper, 8 AWG has a 50 A rating in the 75°C column, so it works when the breaker and equipment terminals are listed for 75°C. Otherwise use the 60°C column, where 6 AWG (55 A) is needed. Aluminum needs larger sizes. Long runs may need a larger size still for voltage drop.
Is aluminum wire safe to use? +
Modern aluminum conductors (AA-8000 series alloys) are widely used for feeders and services, sized larger than copper for the same current. They must be used with terminals rated for aluminum (marked AL or CU/AL) and installed per the manufacturer's torque and anti-oxidant instructions.